Periodic transformer failure
  #1
Old 10-04-2006, 06:59 PM
vMike
Junior Member


vMike is offline
vMike's Info
Join Date: Oct 2006
Posts: 3
Default Periodic transformer failure

I have a 120v to 24vac transformer for a lawn sprinkler system that has
failed about 3 times since I purchased the house. This time I took the
windings apart and found the break in the 120v winding. I live in a
lightening prone area. Is this failure most likely from power surges or is
there some other possible cause.

Thanks.

Mike



Reply With Quote
Periodic transformer failure
  #2
Old 10-04-2006, 11:35 PM
Venus
Junior Member


Venus is offline
Venus's Info
Join Date: Oct 2006
Posts: 3
Default Periodic transformer failure


"vMike" <MicZhaYel.GeoZrgeY@noYandZ.geZwaYrrenZ.com> wrote in message
news:zy_Ug.40722$KR1.34654@bignews2.bellsouth.net. ..
Quote:
I have a 120v to 24vac transformer for a lawn sprinkler system that has failed about 3 times since I purchased the house. This time I took the windings apart and found the break in the 120v winding. I live in a lightening prone area. Is this failure most likely from power surges or is there some other possible cause. Thanks. Mike



I do not think the lightning is the cause, I think it was caused by the
overheating of the transformer itself, this happened because the transformer
is rate too low for your load. Check the voltage before applying the load,
and then apply the load to see its voltage drop. If the drop 40% or more
then, you'll need to buy a bigger transformer, do not buy the exact model.



Cam



Reply With Quote
Periodic transformer failure
  #3
Old 10-05-2006, 01:25 AM
vMike
Junior Member


vMike is offline
vMike's Info
Join Date: Oct 2006
Posts: 3
Default Periodic transformer failure


"Venusē" <123@PlanetUranus.com> wrote in message
news:452483d0_1@newsfeed.slurp.net...
Quote:
"vMike" <MicZhaYel.GeoZrgeY@noYandZ.geZwaYrrenZ.com> wrote in message news:zy_Ug.40722$KR1.34654@bignews2.bellsouth.net. ..
Quote:
I have a 120v to 24vac transformer for a lawn sprinkler system that has failed about 3 times since I purchased the house. This time I took the windings apart and found the break in the 120v winding. I live in a lightening prone area. Is this failure most likely from power surges or is there some other possible cause. Thanks. Mike
I do not think the lightning is the cause, I think it was caused by the overheating of the transformer itself, this happened because the transformer is rate too low for your load. Check the voltage before applying the load, and then apply the load to see its voltage drop. If the drop 40% or more then, you'll need to buy a bigger transformer, do not buy the exact model. Cam

The transformer was an original factory replacement part. Do I check the
voltage drop on the load side or the line side? The control box is outside
and in sun in the morning when the sprinklers are on, could the sun cause
the overheating.
Mike


Reply With Quote
Periodic transformer failure
  #4
Old 10-05-2006, 07:37 AM
Venus
Junior Member


Venus is offline
Venus's Info
Join Date: Oct 2006
Posts: 3
Default Periodic transformer failure


"vMike" <MicZhaYel.GeoZrgeY@noYandZ.geZwaYrrenZ.com> wrote in message
news:ic4Vg.18272$GY5.3666@bignews6.bellsouth.net.. .
Quote:
"Venusē" <123@PlanetUranus.com> wrote in message news:452483d0_1@newsfeed.slurp.net...
Quote:
"vMike" <MicZhaYel.GeoZrgeY@noYandZ.geZwaYrrenZ.com> wrote in message news:zy_Ug.40722$KR1.34654@bignews2.bellsouth.net. ..
Quote:
I have a 120v to 24vac transformer for a lawn sprinkler system that has failed about 3 times since I purchased the house. This time I took the windings apart and found the break in the 120v winding. I live in a lightening prone area. Is this failure most likely from power surges or is there some other possible cause. Thanks. Mike
I do not think the lightning is the cause, I think it was caused by the overheating of the transformer itself, this happened because the transformer is rate too low for your load. Check the voltage before applying the load, and then apply the load to see its voltage drop. If the drop 40% or more then, you'll need to buy a bigger transformer, do not buy the exact model. Cam
The transformer was an original factory replacement part. Do I check the voltage drop on the load side or the line side? The control box is outside and in sun in the morning when the sprinklers are on, could the sun cause the overheating. Mike


The Sun could add more heat to it while in operation. You would check the
secondary (output side 24Vac)

It should not drop so much, (10% is typical 21volts) 40% = 14.4 Volts or
lower is terrible. I've seen these transformers before at Home Depot, they
look small to me for continuous operation. I have it too for door bell,
door bell is low load, that's why I don't have problem with it. Yours must
have a big and continuous load, that's why you're having a problem
statically (because in a coil, high voltage is self-generated through energy
delay release, this may be why it jumps between the wire after overheating.



Cam






Reply With Quote
Periodic transformer failure
  #5
Old 10-05-2006, 02:20 PM
vMike
Junior Member


vMike is offline
vMike's Info
Join Date: Oct 2006
Posts: 3
Default Periodic transformer failure

>>>
Quote:
I do not think the lightning is the cause, I think it was caused by the overheating of the transformer itself, this happened because the transformer is rate too low for your load. Check the voltage before applying the load, and then apply the load to see its voltage drop. If the drop 40% or more then, you'll need to buy a bigger transformer, do not buy the exact model. Cam The transformer was an original factory replacement part. Do I check the voltage drop on the load side or the line side? The control box is outside and in sun in the morning when the sprinklers are on, could the sun cause the overheating. Mike The Sun could add more heat to it while in operation. You would check the secondary (output side 24Vac) It should not drop so much, (10% is typical 21volts) 40% = 14.4 Volts or lower is terrible. I've seen these transformers before at Home Depot, they look small to me for continuous operation. I have it too for door bell, door bell is low load, that's why I don't have problem with it. Yours must have a big and continuous load, that's why you're having a problem statically (because in a coil, high voltage is self-generated through energy delay release, this may be why it jumps between the wire after overheating. Cam



I narrowed the problem to one zone using your suggestion. The voltage
dropped on one zone from around 24v to 15. All of the others had only a 1
volt drop. Next I need to narrow it down to the zone wiring or the box. I
am going to switch two zones and see what happens. If that doesn't work I
will switch the solenoid. I just hope it isn't the wire to the solenoid.

Mike


Reply With Quote
Periodic transformer failure
  #6
Old 10-06-2006, 06:37 PM
Venusē
Junior Member


Venusē is offline
Venusē's Info
Join Date: Oct 2006
Posts: 1
Default Periodic transformer failure


"vMike" <MicZhaYel.GeoZrgeY@noYandZ.geZwaYrrenZ.com> wrote in message
news:fzfVg.15256$zF5.8439@bignews1.bellsouth.net.. .
Quote:
>> I do not think the lightning is the cause, I think it was caused by the> overheating of the transformer itself, this happened because the> transformer is rate too low for your load. Check the voltage before> applying the load, and then apply the load to see its voltage drop.> If the drop 40% or more then, you'll need to buy a bigger transformer,> do not buy the exact model.>>>> Cam> The transformer was an original factory replacement part. Do I check the voltage drop on the load side or the line side? The control box is outside and in sun in the morning when the sprinklers are on, could the sun cause the overheating. Mike The Sun could add more heat to it while in operation. You would check the secondary (output side 24Vac) It should not drop so much, (10% is typical 21volts) 40% = 14.4 Volts or lower is terrible. I've seen these transformers before at Home Depot, they look small to me for continuous operation. I have it too for door bell, door bell is low load, that's why I don't have problem with it. Yours must have a big and continuous load, that's why you're having a problem statically (because in a coil, high voltage is self-generated through energy delay release, this may be why it jumps between the wire after overheating. Cam I narrowed the problem to one zone using your suggestion. The voltage dropped on one zone from around 24v to 15. All of the others had only a 1 volt drop. Next I need to narrow it down to the zone wiring or the box. I am going to switch two zones and see what happens. If that doesn't work I will switch the solenoid. I just hope it isn't the wire to the solenoid. Mike


Sorry my news server was down. That's a good idea by narrowing down to a
particular zone. If one Zone took that much current then, chances are you
got a heavy load someone, plus voltage drop to 15V is not a healthy sign.



-Cam




Reply With Quote
There is a good news to tell you
  #7
Old 07-20-2008, 06:59 PM
bcde339
Junior Member


bcde339 is offline
bcde339's Info
Join Date: Jul 2008
Posts: 23
Default There is a good news to tell you

Tell you two good Web site, anyone can find here sex, is a AdultFriendFinder, Lesbian is another.

Today, burnt drugs include: 1,254 grams of heroin, 8,574 grams of Ketamine, 4,005 grams of methamphetamine, Ma Ancient 1,168 grams (12530), ecstasy, 95 grams (411), 36 grams of marijuana, 35 grams of caffeine, together 15,167 grams. The Public Security Bureau in charge of urban leadership, UNODC head, urban representatives of the Public Security Bureau police.
Reply With Quote
buy plus size wedding dresses online.
  #8
Old 07-22-2008, 04:22 AM
jormabridal
Member


jormabridal is offline
jormabridal's Info
Join Date: Jul 2008
Posts: 30
Talking buy plus size wedding dresses online.

great.
provide plus size wedding dresses.
we are a professional wedding dresses factory, provide plus wedding dresses for some people with larger size, if you don't know where buy, you can contact with us for free. we accept custom cust order, and free custom cust cost no tax.
we also sale wedding gowns, bridal gowns and wedding dress.
if our information not useful, you can cancel them.
thanks!
__________________
jorma wedding dress factory
Reply With Quote
Reply


Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

vB code is On
Smilies are On
[IMG] code is On
HTML code is Off
Forum Jump



Powered by: vBulletin Version 3.0.7
Copyright ©2000 - 2008, Jelsoft Enterprises Ltd.
Style Design by vBStyles.com


Top Contact Us - Home Improvement Forums- Archive - MyLounge Top
MyLounge.com Site Map
Forum: Cars, Cell Phone, Database, Games, Home Improvement, IT, Music, School, Sports, Web Design, Web Server, Weight Loss

The MyLounge.com forum is intended for informational use only and should not be relied upon and is not a substitute for any advice. The information contained on MyLounge.com are opinions and suggestions of members and is not a representation of the opinions of MyLounge.com. MyLounge.com does not warrant or vouch for the accuracy, completeness or usefulness of any postings or the qualifications of any person responding. Please consult a expert or seek the services of an attorney in your area for more accuracy on your specific situation. Please note that our forums also serve as mirrors to Usenet newsgroups. Many posts you see on our forums are made by newsgroup users who may not be members of MyLounge.com Term of Service